          Programmable Logic Controller

          KV Nano series

          Select Language

          Terminal block type: Base unit, 14-point, Transistor output type

          Model

          KV-N14AT

          KV-N14ATP

          KV-N14DT

          KV-N14DTP

          General specifications

          Supply voltage

          100 to 240 VAC (+10%/-15%)

          24 VDC (+10%/-15%)

          Output power supply voltage

          24 VDC (±10%; output capacity: 0.6 A)

          -

          Operating ambient temperature

          0 to 55°C (no freezing)*1*2

          Storage temperature

          -25 to +75°C

          Operating ambient humidity

          5 to 95% RH (no condensation)*1

          Withstand voltage

          1500 VAC for 1 minute, between power supply terminal and I/O terminals and between all external terminals and case

          Noise immunity

          1500 V peak-to-peak or more, pulse width 1 µs, 50 ns (by noise simulator), IEC standard compliant (IEC61000-4-2/3/4/6)

          Vibration resistance

          Intermittent vibration

          Frequency: 5 to 9 Hz

          Amplitude: 3.5 mm*3*4

          Frequency: 9 to 150 Hz

          Acceleration: 9.8 m/s2*3*5

          Continuous vibration

          Frequency: 5 to 9 Hz

          Amplitude: 1.75 mm*3*5

          Frequency: 9 to 150 Hz

          Acceleration: 4.9 m/s2*3*5

          Shock resistance

          Acceleration: 150 m/s2, application time: 11 ms, two times in each of the X, Y, and Z directions

          Insulation resistance

          50 MΩ or more
          (500 VDC megger used to perform measurements between power terminal and input terminals, and between all external terminals and case)

          Operating environment

          As little dust and corrosive gases as possible

          Operating altitude

          2000 m or less

          Overvoltage category

          AC: II, DC: I

          Pollution degree

          2

          Performance specifications

          Calculation control method

          Programme storage method

          I/O control method

          Refresh method

          Programming language

          Expanded ladder, KV Script, mnemonic

          Number of instructions

          Basic instructions: 81 kinds and 182 instructions, Application instructions: 39 kinds and 56 instructions
          Calculation instructions: 123 kinds and 311 instructions, Expansion instructions: 92 kinds and 141 instructions,
          Total: 335 kinds and 690 instructions

          Instruction execution speed

          Basic instruction: 50 ns minimum, Application instruction: 170 ns minimum

          Program capacity

          8k steps

          Maximum number of attachable I/O units

          3

          Maximum number of I/O points

          128 (excluding the base unit I/O)

          Input relay/Output relay/Internal auxiliary relay

          R

          Total of 9600 points 1 bit (R000 to R59915)

          Link relay

          B

          8192 points 1 bit (B0 to B1FFF)

          Internal auxiliary relay

          MR

          9600 points 1 bit (MR000 to MR59915)

          Latch relay

          LR

          3200 points 1 bit (LR000 to LR19915)

          Control relay

          CR

          1440 points 1 bit (CR000 to CR8915)

          Timer

          T

          512 points 32 bits (T0 to T511)

          Counter

          C

          256 points 32 bits (C0 to C255)

          Data memory

          DM

          32768 points 16 bits (DM0 to DM32767)

          Link register

          W

          16384 points 16 bits (W0 to W3FFF)

          Temporary memory

          TM

          512 points 16 bits (TM0 to TM511)

          High-speed counter

          CTH

          2 points (CTH0 and CTH1)
          32-bit automatic reset counter*6 (Input response: 100 kHz per single phase, 50 kHz per phase difference)*7

          High-speed
          counter comparator

          CTC

          4 points (CTC0 to CTC3)
          32 bits, two points per high-speed counter

          Index register

          Z

          12 points 32 bits (Z01 to Z12)

          Control memory

          CM

          9000 points 16 bits (CM0 to CM8999)

          Positioning pulse output

          2 axes
          Maximum output frequency: 100 kHz

          Base unit I/O

          Input: 8 points, output: 6 points
          Input common: 1 point, Output common: 4 points (R type)/1 point (T/TP type)

          Number of comments and
          labels that can be stored
          in the main unit

          Device comment

          10000
          When a maximum-length ladder programme is written with no labels.

          Label

          14000
          When a maximum-length ladder programme is written with no device comments.

          Power off hold function

          Programme memory

          Flash ROM can be rewritten 10000 times

          Device

          Nonvolatile RAM*8

          Self-diagnosis function

          CPU error, RAM error, and other problems

          Input specifications

          Relay number

          General input: R000 to R003 (4 points), High-speed A-phase and B-phase input: R004 to R007 (2 channels, 4 points in total)

          Input mode

          24 VDC input (open collector)

          Maximum input voltage

          26.4 VDC

          Rated input voltage

          24 VDC (General input: 5.3 mA, High-speed A-phase and B-phase input: 6.5 mA*9)

          Minimum ON voltage

          19 VDC

          Maximum OFF current

          1.5 mA

          Common method

          General input: All inputs/common (1 terminal)
          High-speed A-phase and B-phase input: Shared common for all points (shared with general input)

          Circuit delay time

          General input:
          OFF to ON: Max. 30 µs (Typ. 3.5 µs), ON to OFF: Max. 50 µs (Typ. 15 µs)
          High-speed A-phase and B-phase input:
          OFF to ON: Max. 2 µs (Typ. 1.1 µs), ON to OFF: Max. 2 µs (Typ. 0.3 µs)*10

          Input time constant

          Normal: 10 ms, When the HSP instruction is used: 10 µs
          When CR2305 is turned ON: 10 µs to 10 ms, eight-level switching is possible (set with CM1620). Can also be set from the Unit Editor.*10

          Delay by input time constant
          Input time constant setting 10 µs: Digital filter 1.6 to 2 µs
          Input time constant setting 20 µs: Digital filter 9 to 12 µss
          Input time constant setting 110 µs: Digital filter 90 to 93 µs
          Input time constant setting 500 µs: Digital filter 300 to 400 µs
          Input time constant setting 1 ms: Digital filter 800 to 900 µs
          Input time constant setting 2.5 ms: Digital filter 2.3 to 2.4 ms
          Input time constant setting 5 ms: Digital filter 4.0 to 4.5 ms
          Input time constant setting 10 ms: Digital filter 9 to 9.5 ms

          Response frequency

          (High-speed A-phase and B-phase input) Single phase: 100 kHz, phase difference: 50 kHz, 24 V±10%, Duty 50%

          Output specifications

          Relay number

          General output: R504 to R505 (2 points), High-speed output: R500 to R503 (4 points)

          Output mode

          Sink output type
          MOSFET (N-ch) output

          Source output type
          MOSFET (P-ch) output

          Sink output type
          MOSFET (N-ch) output

          Source output type
          MOSFET (P-ch) output

          Rated load

          30 VDC, 0.5 A

          Maximum OFF voltage

          30 VDC

          Leakage current at OFF

          100 µA or less

          Residual voltage at ON

          0.8 VDC or less (with 0.5 A output), 0.6 VDC or less (with 0.3 A output)

          Common method

          8 to 10 points/1 common

          ON/OFF response time

          General output:
          OFF to ON : 100 µs (load of 1 mA or more), ON to OFF : 200 µs (load of 1 mA or more)
          High-speed output:
          OFF to ON: 2 µs (7 to 100 mA load), ON to OFF: 5 µs (7 to 100 mA load)

          Overcurrent protection

          Protection provided for each common*11

          Output frequency

          High-speed output: 100 kHz (7 to 100 mA load)

          Built-in serial port

          Interface

          Communication standard

          RS-232C

          Connection

          Modular connector

          Transmission specifications RS-232C

          Baud rate

          1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps

          Transmission method

          Full duplex

          Data format

          Start bit

          1 bit

          Data bits

          7 bits, 8 bits

          Stop bits

          1 bit, 2 bits

          Error detection

          Parity

          Even, odd, none

          Transmission distance

          15 m

          Number of transmission units

          1

          Indication

          SD (green), RD (red)

          Internal current consumption

          75 VA (VA is calculated with a power factor of 30%.)

          150 mA

          Weight

          Approx. 420 g

          Approx. 330 g

          *1 The range guaranteed as a system (excluding items specially noted for the units and cassettes).
          *2 The temperature below the unit centre (30 mm) inside a control panel.
          *3 These specifications correspond to situations in which the unit is mounted on a DIN rail and in which the unit is mounted on the panel directly.
          *4 Conforms to JIS B 3502 and IEC61131-2, Number of scans: 10 times (100 minutes) in each of the X, Y, and Z directions
          *5 Conforms to JIS B 3502 and IEC61131-2. Number of scans: 10 times (100 minutes) in each of the X, Y, and Z directions
          *6 You can also configure the settings so that automatic reset is not used.
          *7 Only open collectors are supported. Line drivers are not supported.
          *8 You can set the target device by clicking "CPU system setting" and then "Power off holding" in KV STUDIO.
          *9 Reference value of input current.
          *10 The input response time corresponding to the input time constant can be calculated as shown below. (Response time) = (Circuit delay of the input circuit) + (Delay by the digital filter)
          Example: Maximum response time when the input time constant is set to 500 µs
          OFF to ON: 30 µs (circuit delay) + 400 µs (digital filter) = 430 µs, ON to OFF: 50 µs (circuit delay) + 400 µs (digital filter) = 450 µs
          *11 If an overcurrent occurs, the protection operation (output turned OFF) and automatic recovery are repeated for all outputs within the shared common until the cause of the problem is removed.

          Terminal block type: Base unit, 24-point, Transistor output type

          Model

          KV-N24AT

          KV-N24ATP

          KV-N24DT

          KV-N24DTP

          General specifications

          Supply voltage

          100 to 240 VAC (+10%/-15%)

          24 VDC (+10%/-15%)

          Output power supply voltage

          24 VDC (±10%; output capacity: 0.6 A)

          -

          Operating ambient temperature

          0 to 55°C (no freezing)*1*2

          Storage temperature

          -25 to +75°C

          Operating ambient humidity

          5 to 95% RH (no condensation)*1

          Withstand voltage

          1500 VAC for 1 minute, between power supply terminal and I/O terminals and between all external terminals and case

          Noise immunity

          1500 V peak-to-peak or more, pulse width 1 µs, 50 ns (by noise simulator), IEC standard compliant (IEC61000-4-2/3/4/6)

          Vibration resistance

          Intermittent vibration

          Frequency: 5 to 9 Hz

          Amplitude: 3.5 mm*3*4

          Frequency: 9 to 150 Hz

          Acceleration: 9.8 m/s2*3*5

          Continuous vibration

          Frequency: 5 to 9 Hz

          Amplitude: 1.75 mm*3*5

          Frequency: 9 to 150 Hz

          Acceleration: 4.9 m/s2*3*5

          Shock resistance

          Acceleration: 150 m/s2, application time: 11 ms, two times in each of the X, Y, and Z directions

          Insulation resistance

          50 MΩ or more
          (500 VDC megger used to perform measurements between power terminal and input terminals, and between all external terminals and case)

          Operating environment

          As little dust and corrosive gases as possible

          Operating altitude

          2000 m or less

          Overvoltage category

          AC: II, DC: I

          Pollution degree

          2

          Performance specifications

          Calculation control method

          Programme storage method

          I/O control method

          Refresh method

          Programming language

          Expanded ladder, KV Script, mnemonic

          Number of instructions

          Basic instructions: 81 kinds and 182 instructions, Application instructions: 39 kinds and 56 instructions
          Calculation instructions: 123 kinds and 311 instructions, Expansion instructions: 92 kinds and 141 instructions,
          Total: 335 kinds and 690 instructions

          Instruction execution speed

          Basic instruction: 50 ns minimum, Application instruction: 170 ns minimum

          Program capacity

          8k steps

          Maximum number of attachable I/O units

          8

          Maximum number of I/O points

          256 (excluding the base unit I/O)

          Input relay/Output relay/Internal auxiliary relay

          R

          Total of 9600 points 1 bit (R000 to R59915)

          Link relay

          B

          8192 points 1 bit (B0 to B1FFF)

          Internal auxiliary relay

          MR

          9600 points 1 bit (MR000 to MR59915)

          Latch relay

          LR

          3200 points 1 bit (LR000 to LR19915)

          Control relay

          CR

          1440 points 1 bit (CR000 to CR8915)

          Timer

          T

          512 points 32 bits (T0 to T511)

          Counter

          C

          256 points 32 bits (C0 to C255)

          Data memory

          DM

          32768 points 16 bits (DM0 to DM32767)

          Link register

          W

          16384 points 16 bits (W0 to W3FFF)

          Temporary memory

          TM

          512 points 16 bits (TM0 to TM511)

          High-speed counter

          CTH

          2 points (CTH0 and CTH1)
          32-bit automatic reset counter*6 (Input response: 100 kHz per single phase, 50 kHz per phase difference)*7

          High-speed
          counter comparator

          CTC

          4 points (CTC0 to CTC3)
          32 bits, two points per high-speed counter

          Index register

          Z

          12 points 32 bits (Z01 to Z12)

          Control memory

          CM

          9000 points 16 bits (CM0 to CM8999)

          Positioning pulse output

          2 axes
          Maximum output frequency: 100 kHz

          Base unit I/O

          Input: 14 points; output: 10 points
          Input common: 1 point, Output common: 5 points (R type)/1 point (T/TP type)

          Number of comments and
          labels that can be stored
          in the main unit

          Device comment

          20000
          When a maximum-length ladder programme is written with no labels.

          Label

          28000
          When a maximum-length ladder programme is written with no device comments.

          Power off hold function

          Programme memory

          Flash ROM can be rewritten 10000 times

          Device

          Nonvolatile RAM*8

          Self-diagnosis function

          CPU error, RAM error, and other problems

          Input specifications

          Relay number

          General input: R000 to R003, R008 to R013 (10 points)
          High-speed A-phase and B-phase input: R004 to R007 (2 channels, 4 points in total)

          Input mode

          24 VDC input (open collector)

          Maximum input voltage

          26.4 VDC

          Rated input voltage

          24 VDC (General input: 5.3 mA, High-speed A-phase and B-phase input: 6.5 mA*9)

          Minimum ON voltage

          19 VDC

          Maximum OFF current

          1.5 mA

          Common method

          General input: All inputs/common (1 terminal)
          High-speed A-phase and B-phase input: Shared common for all points (shared with general input)

          Circuit delay time

          General input:
          OFF to ON: Max. 30 µs (Typ. 3.5 µs), ON to OFF: Max. 50 µs (Typ. 15 µs)
          High-speed A-phase and B-phase input:
          OFF to ON: Max. 2 µs (Typ. 1.1 µs), ON to OFF: Max. 2 µs (Typ. 0.3 µs)*10

          Input time constant

          Normal: 10 ms, When the HSP instruction is used: 10 µs
          When CR2305 is turned ON: 10 µs to 10 ms, eight-level switching is possible (set with CM1620). Can also be set from the Unit Editor.*10

          Delay by input time constant
          Input time constant setting 10 µs: Digital filter 1.6 to 2 µs
          Input time constant setting 20 µs: Digital filter 9 to 12 µss
          Input time constant setting 110 µs: Digital filter 90 to 93 µs
          Input time constant setting 500 µs: Digital filter 300 to 400 µs
          Input time constant setting 1 ms: Digital filter 800 to 900 µs
          Input time constant setting 2.5 ms: Digital filter 2.3 to 2.4 ms
          Input time constant setting 5 ms: Digital filter 4.0 to 4.5 ms
          Input time constant setting 10 ms: Digital filter 9 to 9.5 ms

          Response frequency

          (High-speed A-phase and B-phase input) Single phase: 100 kHz, phase difference: 50 kHz, 24 V±10%, Duty 50%

          Output specifications

          Relay number

          General output: R504 to R509 (6 points), High-speed output: R500 to R503 (4 points)

          Output mode

          Sink output type
          MOSFET (N-ch) output

          Source output type
          MOSFET (P-ch) output

          Sink output type
          MOSFET (N-ch) output

          Source output type
          MOSFET (P-ch) output

          Rated load

          30 VDC, 0.5 A

          Maximum OFF voltage

          30 VDC

          Leakage current at OFF

          100 µA or less

          Residual voltage at ON

          0.8 VDC or less (with 0.5 A output), 0.6 VDC or less (with 0.3 A output)

          Common method

          8 to 10 points/1 common

          ON/OFF response time

          General output:
          OFF to ON : 100 µs (load of 1 mA or more), ON to OFF : 200 µs (load of 1 mA or more)
          High-speed output:
          OFF to ON: 2 µs (7 to 100 mA load), ON to OFF: 5 µs (7 to 100 mA load)

          Overcurrent protection

          Protection provided for each common*11

          Output frequency

          High-speed output: 100 kHz (7 to 100 mA load)

          Built-in serial port

          Interface

          Communication standard

          RS-232C

          Connection

          Modular connector

          Transmission specifications RS-232C

          Baud rate

          1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps

          Transmission method

          Full duplex

          Data format

          Start bit

          1 bit

          Data bits

          7 bits, 8 bits

          Stop bits

          1 bit, 2 bits

          Error detection

          Parity

          Even, odd, none

          Transmission distance

          15 m

          Number of transmission units

          1

          Indication

          SD (green), RD (red)

          Internal current consumption

          76 VA (VA is calculated with a power factor of 30%.)

          160 mA

          Weight

          Approx. 470 g

          Approx. 390 g

          *1 The range guaranteed as a system (excluding items specially noted for the units and cassettes).
          *2 The temperature below the unit centre (30 mm) inside a control panel.
          *3 These specifications correspond to situations in which the unit is mounted on a DIN rail and in which the unit is mounted on the panel directly.
          *4 Conforms to JIS B 3502 and IEC61131-2, Number of scans: 10 times (100 minutes) in each of the X, Y, and Z directions
          *5 Conforms to JIS B 3502 and IEC61131-2. Number of scans: 10 times (100 minutes) in each of the X, Y, and Z directions
          *6 You can also configure the settings so that automatic reset is not used.
          *7 Only open collectors are supported. Line drivers are not supported.
          *8 You can set the target device by clicking "CPU system setting" and then "Power off holding" in KV STUDIO.
          *9 Reference value of input current.
          *10 The input response time corresponding to the input time constant can be calculated as shown below. (Response time) = (Circuit delay of the input circuit) + (Delay by the digital filter)
          Example: Maximum response time when the input time constant is set to 500 µs
          OFF to ON: 30 µs (circuit delay) + 400 µs (digital filter) = 430 µs, ON to OFF: 50 µs (circuit delay) + 400 µs (digital filter) = 450 µs
          *11 If an overcurrent occurs, the protection operation (output turned OFF) and automatic recovery are repeated for all outputs within the shared common until the cause of the problem is removed.

          Terminal block type: Base unit, 40/60-point, Transistor output type

          Model

          KV-N40AT

          KV-N40ATP

          KV-N40DT

          KV-N40DTP

          KV-N60AT

          KV-N60ATP

          General specifications

          Supply voltage

          100 to 240 VAC (+10%/-15%)

          24 VDC (+10%/-15%)

          100 to 240 VAC (+10%/-15%)

          Output power supply voltage

          24 VDC (±10%; output capacity: 0.6 A)

          -

          24 VDC (±10%; output capacity: 0.6 A)

          Operating ambient temperature

          0 to 55°C (no freezing)*1*2

          Storage temperature

          -25 to +75°C

          Operating ambient humidity

          5 to 95% RH (no condensation)*1

          Withstand voltage

          1500 VAC for 1 minute, between power supply terminal and I/O terminals and between all external terminals and case

          Noise immunity

          1500 V peak-to-peak or more, pulse width 1 µs, 50 ns (by noise simulator), IEC standard compliant (IEC61000-4-2/3/4/6)

          Vibration resistance

          Intermittent vibration

          Frequency: 5 to 9 Hz

          Amplitude: 3.5 mm*3*4

          Frequency: 9 to 150 Hz

          Acceleration: 9.8 m/s2*3*5

          Continuous vibration

          Frequency: 5 to 9 Hz

          Amplitude: 1.75 mm*3*5

          Frequency: 9 to 150 Hz

          Acceleration: 4.9 m/s2*3*5

          Shock resistance

          Acceleration: 150 m/s2, application time: 11 ms, two times in each of the X, Y, and Z directions

          Insulation resistance

          50 MΩ or more
          (500 VDC megger used to perform measurements between power terminal and input terminals, and between all external terminals and case)

          Operating environment

          As little dust and corrosive gases as possible

          Operating altitude

          2000 m or less

          Overvoltage category

          AC: II, DC: I

          Pollution degree

          2

          Performance specifications

          Calculation control method

          Programme storage method

          I/O control method

          Refresh method

          Programming language

          Expanded ladder, KV Script, mnemonic

          Number of instructions

          Basic instructions: 81 kinds and 182 instructions, Application instructions: 39 kinds and 56 instructions
          Calculation instructions: 123 kinds and 311 instructions, Expansion instructions: 92 kinds and 141 instructions,
          Total: 335 kinds and 690 instructions

          Instruction execution speed

          Basic instruction: 50 ns minimum, Application instruction: 170 ns minimum

          Program capacity

          16k steps

          Maximum number of attachable I/O units

          8

          Maximum number of I/O points

          256 (excluding the base unit I/O)

          Input relay/Output relay/Internal auxiliary relay

          R

          Total of 9600 points 1 bit (R000 to R59915)

          Link relay

          B

          8192 points 1 bit (B0 to B1FFF)

          Internal auxiliary relay

          MR

          9600 points 1 bit (MR000 to MR59915)

          Latch relay

          LR

          3200 points 1 bit (LR000 to LR19915)

          Control relay

          CR

          1440 points 1 bit (CR000 to CR8915)

          Timer

          T

          512 points 32 bits (T0 to T511)

          Counter

          C

          256 points 32 bits (C0 to C255)

          Data memory

          DM

          32768 points 16 bits (DM0 to DM32767)

          Link register

          W

          16384 points 16 bits (W0 to W3FFF)

          Temporary memory

          TM

          512 points 16 bits (TM0 to TM511)

          High-speed counter

          CTH

          3 points (CTH0 to CTH2)
          32-bit automatic reset counter*6 (Input response: 100 kHz per single phase, 50 kHz per phase difference)*7

          4 points (CTH0 to CTH3)
          32-bit automatic reset counter*6 (Input response: 100 kHz per single phase, 50 kHz per phase difference)*7

          High-speed
          counter comparator

          CTC

          6 points (CTC0 to CTC5)
          32 bits, two points per high-speed counter

          8 points (CTC0 to CTC7)
          32 bits, two points per high-speed counter

          Index register

          Z

          12 points 32 bits (Z01 to Z12)

          Control memory

          CM

          9000 points 16 bits (CM0 to CM8999)

          Positioning pulse output

          3 axes
          Maximum output frequency: 100 kHz

          4 axes
          Maximum output frequency: 100 kHz

          Base unit I/O

          Input: 24 points, output: 16 points
          Input common: 1 point, Output common: 6 points (R type)/2 points (T/TP type)

          Input: 36 points, output: 24 points
          Input common: 1 point, Output common: 8 points (R type)/3 points (T/TP type)

          Number of comments and
          labels that can be stored
          in the main unit

          Device comment

          20000
          When a maximum-length ladder programme is written with no labels.

          Label

          28000
          When a maximum-length ladder programme is written with no device comments.

          Power off hold function

          Programme memory

          Flash ROM can be rewritten 10000 times

          Device

          Nonvolatile RAM*8

          Self-diagnosis function

          CPU error, RAM error, and other problems

          Input specifications

          Relay number

          General input: R000 to R007, R014 to R107 (18 points)
          High-speed A-phase and B-phase input: R008 to R013 (3 channels, 6 points in total)

          General input: R000 to R007, R100 to R203 (28 points)*12
          High-speed A-phase and B-phase input: R008 to R015 (4 channels, 8 points in total)

          Input mode

          24 VDC input (open collector)

          Maximum input voltage

          26.4 VDC

          Rated input voltage

          24 VDC (General input: 5.3 mA, High-speed A-phase and B-phase input: 6.5 mA*9)

          Minimum ON voltage

          19 VDC

          Maximum OFF current

          1.5 mA

          Common method

          General input: All inputs/common (1 terminal)
          High-speed A-phase and B-phase input: Shared common for all points (shared with general input)

          Circuit delay time

          General input:
          OFF to ON: Max. 30 µs (Typ. 3.5 µs), ON to OFF: Max. 50 µs (Typ. 15 µs)
          High-speed A-phase and B-phase input:
          OFF to ON: Max. 2 µs (Typ. 1.1 µs), ON to OFF: Max. 2 µs (Typ. 0.3 µs)*10

          General input (below for R108 to R203):
          OFF to ON: Max. 50 µs (Typ. 7 µs), ON to OFF: Max. 150 µs (Typ. 70 µs)
          High-speed A-phase and B-phase input
          OFF to ON: Max. 2 µs (Typ. 1.1 µs), ON to OFF: Max. 2 µs (Typ. 0.3 µs)*10

          Input time constant

          Normal: 10 ms, When the HSP instruction is used: 10 µs
          When CR2305 is turned ON: 10 µs to 10 ms, eight-level switching is possible (set with CM1620). Can also be set from the Unit Editor.*10

          Delay by input time constant
          Input time constant setting 10 µs: Digital filter 1.6 to 2 µs
          Input time constant setting 20 µs: Digital filter 9 to 12 µss
          Input time constant setting 110 µs: Digital filter 90 to 93 µs
          Input time constant setting 500 µs: Digital filter 300 to 400 µs
          Input time constant setting 1 ms: Digital filter 800 to 900 µs
          Input time constant setting 2.5 ms: Digital filter 2.3 to 2.4 ms
          Input time constant setting 5 ms: Digital filter 4.0 to 4.5 ms
          Input time constant setting 10 ms: Digital filter 9 to 9.5 ms

          Response frequency

          (High-speed A-phase and B-phase input) Single phase: 100 kHz, phase difference: 50 kHz, 24 V±10%, Duty 50%

          Output specifications

          Relay number

          General output: R506 to R515 (10 points), High-speed output: R500 to R505 (6 points)

          General output: R508 to R607 (16 points), High-speed output: R500 to R507 (8 points)

          Output mode

          Sink output type
          MOSFET (N-ch) output

          Source output type
          MOSFET (P-ch) output

          Sink output type
          MOSFET (N-ch) output

          Source output type
          MOSFET (P-ch) output

          Sink output type
          MOSFET (N-ch) output

          Source output type
          MOSFET (P-ch) output

          Rated load

          30 VDC, 0.5 A

          Maximum OFF voltage

          30 VDC

          Leakage current at OFF

          100 µA or less

          Residual voltage at ON

          0.8 VDC or less (with 0.5 A output), 0.6 VDC or less (with 0.3 A output)

          Common method

          8 to 10 points/1 common

          ON/OFF response time

          General output:
          OFF to ON : 100 µs (load of 1 mA or more), ON to OFF : 200 µs (load of 1 mA or more)
          High-speed output:
          OFF to ON: 2 µs (7 to 100 mA load), ON to OFF: 5 µs (7 to 100 mA load)

          Overcurrent protection

          Protection provided for each common*11

          Output frequency

          High-speed output: 100 kHz (7 to 100 mA load)

          Built-in serial port

          Interface

          Communication standard

          RS-232C

          Connection

          Modular connector

          Transmission specifications RS-232C

          Baud rate

          1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps

          Transmission method

          Full duplex

          Data format

          Start bit

          1 bit

          Data bits

          7 bits, 8 bits

          Stop bits

          1 bit, 2 bits

          Error detection

          Parity

          Even, odd, none

          Transmission distance

          15 m

          Number of transmission units

          1

          Indication

          SD (green), RD (red)

          Internal current consumption

          82 VA (VA is calculated with a power factor of 30%.)

          250 mA

          85 VA (VA is calculated with a power factor of 30%.)

          Weight

          Approx. 620 g

          Approx. 530 g

          Approx. 750 g

          *1 The range guaranteed as a system (excluding items specially noted for the units and cassettes).
          *2 The temperature below the unit centre (30 mm) inside a control panel.
          *3 These specifications correspond to situations in which the unit is mounted on a DIN rail and in which the unit is mounted on the panel directly.
          *4 Conforms to JIS B 3502 and IEC61131-2, Number of scans: 10 times (100 minutes) in each of the X, Y, and Z directions
          *5 Conforms to JIS B 3502 and IEC61131-2. Number of scans: 10 times (100 minutes) in each of the X, Y, and Z directions
          *6 You can also configure the settings so that automatic reset is not used.
          *7 Only open collectors are supported. Line drivers are not supported.
          *8 You can set the target device by clicking "CPU system setting" and then "Power off holding" in KV STUDIO.
          *9 Reference value of input current.
          *10 The input response time corresponding to the input time constant can be calculated as shown below. (Response time) = (Circuit delay of the input circuit) + (Delay by the digital filter)
          Example: Maximum response time when the input time constant is set to 500 µs
          OFF to ON: 30 µs (circuit delay) + 400 µs (digital filter) = 430 µs, ON to OFF: 50 µs (circuit delay) + 400 µs (digital filter) = 450 µs
          *11 If an overcurrent occurs, the protection operation (output turned OFF) and automatic recovery are repeated for all outputs within the shared common until the cause of the problem is removed.
          *12 The response time increases for R108 to R203.

          Terminal block type: Base unit, Relay output type

          Model

          KV-N14AR

          KV-N14DR

          KV-N24AR

          KV-N24DR

          KV-N40AR

          KV-N40DR

          KV-N60AR

          General specifications

          Supply voltage

          100 to 240 VAC (+10%/-15%)

          24 VDC (+10%/-15%)

          100 to 240 VAC (+10%/-15%)

          24 VDC (+10%/-15%)

          100 to 240 VAC (+10%/-15%)

          24 VDC (+10%/-15%)

          100 to 240 VAC (+10%/-15%)

          Output power supply voltage

          24 VDC (±10%; output capacity: 0.6 A)

          -

          24 VDC (±10%; output capacity: 0.6 A)

          -

          24 VDC (±10%; output capacity: 0.6 A)

          -

          24 VDC (±10%; output capacity: 0.6 A)

          Operating ambient temperature

          0 to 55°C (no freezing)*1*2

          Storage temperature

          -25 to +75°C

          Operating ambient humidity

          5 to 95% RH (no condensation)*1

          Withstand voltage

          1500 VAC for 1 minute, between power supply terminal and I/O terminals and between all external terminals and case

          Noise immunity

          1500 V peak-to-peak or more, pulse width 1 µs, 50 ns (by noise simulator), IEC standard compliant (IEC61000-4-2/3/4/6)

          Vibration resistance

          Intermittent vibration

          Frequency: 5 to 9 Hz

          Amplitude: 3.5 mm*3*4

          Frequency: 9 to 150 Hz

          Acceleration: 9.8 m/s2*3*4

          Continuous vibration

          Frequency: 5 to 9 Hz

          Amplitude: 1.75 mm*3*4

          Frequency: 9 to 150 Hz

          Acceleration: 4.9 m/s2*3*4

          Shock resistance

          Acceleration: 150 m/s2, application time: 11 ms, two times in each of the X, Y, and Z directions

          Insulation resistance

          50 MΩ or more
          (500 VDC megger used to perform measurements between power terminal and input terminals, and between all external terminals and case)

          Operating environment

          As little dust and corrosive gases as possible

          Operating altitude

          2000 m or less

          Overvoltage category

          AC: II, DC: I

          Pollution degree

          2

          Performance specifications

          Calculation control method

          Programme storage method

          I/O control method

          Refresh method

          Programming language

          Expansion ladder, KV script, mnemonic

          Expanded ladder, KV Script, mnemonic

          Number of instructions

          Basic instructions: 81 kinds and 182 instructions, Application instructions: 39 kinds and 56 instructions
          Calculation instructions: 123 kinds and 311 instructions, Expansion instructions: 92 kinds and 141 instructions,
          Total: 335 kinds and 690 instructions

          Instruction execution speed

          Basic instruction: 50 ns minimum, Application instruction: 170 ns minimum

          Program capacity

          8k steps

          16k steps

          Maximum number of attachable I/O units

          3

          8

          Maximum number of I/O points

          128 (excluding the base unit I/O)

          256 (excluding the base unit I/O)

          Input relay/Output relay/Internal auxiliary relay

          R

          Total of 9600 points 1 bit (R000 to R59915)

          Link relay

          B

          8192 points 1 bit (B0 to B1FFF)

          Internal auxiliary relay

          MR

          9600 points 1 bit (MR000 to MR59915)

          Latch relay

          LR

          3200 points 1 bit (LR000 to LR19915)

          Control relay

          CR

          1440 points 1 bit (CR000 to CR8915)

          Timer

          T

          512 points 32 bits (T0 to T511)

          Counter

          C

          256 points 32 bits (C0 to C255)

          Data memory

          DM

          32768 points 16 bits (DM0 to DM32767)

          Link register

          W

          16384 points 16 bits (W0 to W3FFF)

          Temporary memory

          TM

          512 points 16 bits (TM0 to TM511)

          High-speed counter

          CTH

          2 points (CTH0 and CTH1)
          32-bit automatic reset counter*5 (Input response: 100 kHz per single phase, 50 kHz per phase difference)*6

          3 points (CTH0 to CTH2)
          32-bit automatic reset counter*5 (Input response: 100 kHz per single phase, 50 kHz per phase difference)*6

          4 points (CTH0 to CTH3)
          32-bit automatic reset counter*5 (Input response: 100 kHz per single phase, 50 kHz per phase difference)*6

          High-speed
          counter comparator

          CTC

          4 points (CTC0 to CTC3)
          32 bits, two points per high-speed counter

          6 points (CTC0 to CTC5)
          32 bits, two points per high-speed counter

          8 points (CTC0 to CTC7)
          32 bits, two points per high-speed counter

          Index register

          Z

          12 points 32 bits (Z01 to Z12)

          Control memory

          CM

          9000 points 16 bits (CM0 to CM8999)

          Base unit I/O

          Input: 8 points, output: 6 points
          Input common: 1 point, Output common: 4 points (R type)/1 point (T/TP type)

          Input: 14 points; output: 10 points
          Input common: 1 point, Output common: 5 points (R type)/1 point (T/TP type)

          Input: 24 points, output: 16 points
          Input common: 1 point, Output common: 6 points (R type)/2 points (T/TP type)

          Input: 36 points, output: 24 points
          Input common: 1 point, Output common: 8 points (R type)/3 points (T/TP type)

          Number of comments and
          labels that can be stored
          in the main unit

          Device comment

          10000
          When a maximum-length ladder programme is written with no labels.

          20000
          When a maximum-length ladder programme is written with no labels.

          Label

          14000
          When a maximum-length ladder programme is written with no device comments.

          28000
          When a maximum-length ladder programme is written with no device comments.

          Power off hold function

          Programme memory

          Flash ROM can be rewritten 10000 times

          Device

          Nonvolatile RAM*7

          Self-diagnosis function

          CPU error, RAM error, and other problems

          Input specifications

          Relay number

          General input: R000 to R003 (4 points), High-speed A-phase and B-phase input: R004 to R007 (2 channels, 4 points in total)

          General input: R000 to R003, R008 to R013 (10 points)
          High-speed A-phase and B-phase input: R004 to R007 (2 channels, 4 points in total)

          General input: R000 to R007, R014 to R107 (18 points)
          High-speed A-phase and B-phase input: R008 to R013 (3 channels, 6 points in total)

          General input: R000 to R007, R100 to R203 (28 points)*10
          High-speed A-phase and B-phase input: R008 to R015 (4 channels, 8 points in total)

          Input mode

          24 VDC input (open collector)

          Maximum input voltage

          26.4 VDC

          Rated input voltage

          24 VDC (General input: 5.3 mA, High-speed A-phase and B-phase input: 6.5 mA*8)

          Minimum ON voltage

          19 VDC

          Maximum OFF current

          1.5 mA

          Common method

          General input: All inputs/common (1 terminal)
          High-speed A-phase and B-phase input: Shared common for all points (shared with general input)

          Circuit delay time

          General input:
          OFF to ON: Max. 30 µs (Typ. 3.5 µs), ON to OFF: Max. 50 µs (Typ. 15 µs)
          High-speed A-phase and B-phase input:
          OFF to ON: Max. 2 µs (Typ. 1.1 µs), ON to OFF: Max. 2 µs (Typ. 0.3 µs)*9

          General input (below for R108 to R203):
          OFF to ON: Max. 50 µs (Typ. 7 µs), ON to OFF: Max. 150 µs (Typ. 70 µs)
          High-speed A-phase and B-phase input
          OFF to ON: Max. 2 µs (Typ. 1.1 µs), ON to OFF: Max. 2 µs (Typ. 0.3 µs)*9

          Input time constant

          Normal: 10 ms, When the HSP instruction is used: 10 µs
          When CR2305 is turned ON: 10 µs to 10 ms, eight-level switching is possible (set with CM1620). Can also be set from the Unit Editor.*9

          Delay by input time constant
          Input time constant setting 10 µs: Digital filter 1.6 to 2 µs
          Input time constant setting 20 µs: Digital filter 9 to 12 µss
          Input time constant setting 110 µs: Digital filter 90 to 93 µs
          Input time constant setting 500 µs: Digital filter 300 to 400 µs
          Input time constant setting 1 ms: Digital filter 800 to 900 µs
          Input time constant setting 2.5 ms: Digital filter 2.3 to 2.4 ms
          Input time constant setting 5 ms: Digital filter 4.0 to 4.5 ms
          Input time constant setting 10 ms: Digital filter 9 to 9.5 ms

          Response frequency

          (High-speed A-phase and B-phase input) Single phase: 100 kHz, phase difference: 50 kHz, 24 V±10%, Duty 50%

          Output specifications

          Relay number

          R500 to R505 (6 points)

          R500 to R509 (10 points)

          R500 to R515 (16 points)

          R500 to R607 (24 points)

          Output mode

          Relay

          Rated load

          250 VAC/30 VDC, 2 A

          Common method

          2 to 4 points/1 common

          ON/OFF response time

          10 ms or less

          ON resistance

          50m Ω or less

          Minimum applicable load

          100 µA/100 mVDC

          Relay life

          Electrical: 100000 cycles or more (20 cycles/minute), Mechanical: 20000000 cycles or more

          Relay replacement

          Impossible

          Built-in serial port

          Interface

          Communication standard

          RS-232C

          Connection

          Modular connector

          Transmission specifications RS-232C

          Baud rate

          1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps

          Transmission method

          Full duplex

          Data format

          Start bit

          1 bit

          Data bits

          7 bits, 8 bits

          Stop bits

          1 bit, 2 bits

          Error detection

          Parity

          Even, odd, none

          Transmission distance

          15 m

          Number of transmission units

          1

          Indication

          SD (green), RD (red)

          Internal current consumption

          76 VA
          (VA is calculated with a power factor of 30%.)

          160 mA

          79 VA
          (VA is calculated with a power factor of 30%.)

          190 mA

          86 VA
          (VA is calculated with a power factor of 30%.)

          280 mA

          91 VA
          (VA is calculated with a power factor of 30%.)

          Weight

          Approx. 430 g

          Approx. 350 g

          Approx. 500 g

          Approx. 420 g

          Approx. 660 g

          Approx. 580 g

          Approx. 820 g

          *1 The range guaranteed as a system (excluding items specially noted for the units and cassettes).
          *2 The temperature below the unit centre (30 mm) inside a control panel.
          *3 These specifications correspond to situations in which the unit is mounted on a DIN rail and in which the unit is mounted on the panel directly.
          *4 Conforms to JIS B 3502 and IEC61131-2. Number of scans: 10 times (100 minutes) in each of the X, Y, and Z directions
          *5 You can also configure the settings so that automatic reset is not used.
          *6 Only open collectors are supported. Line drivers are not supported.
          *7 You can set the target device by clicking "CPU system setting" and then "Power off holding" in KV STUDIO.
          *8 Reference value of input current.
          *9 The input response time corresponding to the input time constant can be calculated as shown below. (Response time) = (Circuit delay of the input circuit) + (Delay by the digital filter)
          Example: Maximum response time when the input time constant is set to 500 µs
          OFF to ON: 30 µs (circuit delay) + 400 µs (digital filter) = 430 µs, ON to OFF: 50 µs (circuit delay) + 400 µs (digital filter) = 450 µs
          *10 The response time increases for R108 to R203.

          Terminal block type: Expansion input unit

          Model

          KV-N8EX

          KV-N16EX

          Expansion input unit

          External connection method

          Terminal block

          Input terminals

          24 VDC mode, 5 VDC mode

          Maximum input voltage

          26.4 VDC

          Input rated voltage

          24 VDC mode

          5.3mA

          5 VDC mode

          1mA

          Minimum ON voltage

          24 VDC mode

          19V

          5 VDC mode

          3.5V

          Maximum OFF voltage

          24 VDC mode

          1.5mA

          5 VDC mode

          1.5V

          Common method

          8 points/1 common (2 terminals)*1

          16 points/1 common (2 terminals)*1

          Input time constant (four-level switching)

          Input time constant setting

          OFF to ON: Typ.

          25µs : 10µs
          300µs : 240µs
          1ms : 1ms
          10ms : 10ms

          OFF to ON: Max.

          25µs : 50µs
          300µs : 290µs
          1ms : 1.2ms
          10ms : 11ms

          ON to OFF: Typ.

          25µs : 50µs
          300µs : 280µs
          1ms : 1ms
          10ms : 10ms

          ON to OFF: Max.

          25µs : 150µs
          300µs : 390µs
          1ms : 1.2ms
          10ms : 11ms

          Input impedance

          4.3kΩ

          Internal current consumption

          20mA or less

          Weight

          Approx. 150 g

          Approx. 220 g

          *1 The KV-N8EX and KV-N16EX have 2 COM terminals, but these are shared internally.

          Terminal block type: Expansion output unit

          Model

          KV-N8ER

          KV-N16ER

          KV-N8ET

          KV-N8ETP

          KV-N16ET

          KV-N16ETP

          Expansion output unit

          Output Points

          8

          16

          8

          16

          External connectionmethod

          Relay

          MOSFET (N-ch)
          (with overcurrent protection function)*3

          External connection method

          Terminal block

          Rated load

          250 VAC/30 VDC, 2 A

          30 VDC, 0.5 A

          Leakage current (when output is OFF)

          100µA or less

          Residual voltage (at ON)

          0.8 VDC or less (with 0.5 A output), 0.6 VDC or less (with 0.3 A output)

          ON resistance

          50mΩ or less

          Common method

          4 points/1 common
          (4 terminals)*1

          4 points/
          1 common
          (8 terminals)*2

          8 points/1 common
          (4 terminals)*4*5

          8 points/
          1 common
          (4 terminals)*6

          16 points/
          1 common
          (8 terminals)*6*7

          Response time

          OFF to ON

          10ms or less

          100 µs or less
          (with a load of 1 mA or more)

          ON to OFF

          200 µs or less
          (with a load of 1 mA or more)

          Relay life

          Electrical : 100000 cycles or more (20 cycles/minute) Mechanical : 20000000 cycles or more

          Relay replacement

          Not possible

          Internal current consumption

          60mA or less

          100mA or less

          30mA or less

          40mA or less

          Weight

          Approx. 230 g

          Approx. 260 g

          Approx. 160 g

          Approx. 210 g

          *1 The KV-NC8ER has four C0s and four C1s, and each set of C0s and C1s is shorted internally.
          (The sets of C0s and C1s are independent.)
          *2 The KV-N16ER has two terminals for each of C0, C1, C2, and C3 respectively, which are shorted internally. (C0, C1, C2, and C3 are independent.)
          *3 If even a single overcurrent is detected, the protection operation (output turned OFF) and automatic recovery are
          repeated for all outputs within the shared common, until the cause of the problem is removed.
          *4 The input COM and output COM terminals are independent.
          *5 The KV-N8EXT has four COM output terminals, but these terminals are shared internally.
          *6 The KV-N8ET(P) and KV-N16ET(P) COM terminals are shorted internally.
          *7 For KV-N16ET(P), the outputs within the shared common which are protected when overcurrents are detected are outputs 000 to 007, or outputs 008 to 015.

          Terminal block type: Expansion I/O unit

          Model

          KV-N8EXR

          KV-N8EXT

          Expansion input unit

          External connection method

          Terminal block

          Input Points

          8

          Input terminals

          24 VDC mode, 5 VDC mode

          Maximum input voltage

          26.4 VDC

          Input rated voltage

          24 VDC mode

          5.3mA

          5 VDC mode

          1mA

          Minimum ON voltage

          24 VDC mode

          19V

          5 VDC mode

          3.5V

          Maximum OFF voltage

          24 VDC mode

          1.5mA

          5 VDC mode

          1.5V

          Common method

          8 points/1 common (1 terminal)*1

          8 points/1 common (2 terminals)*1

          Input time constant (four-level switching)

          Input time constant setting

          OFF to ON: Typ.

          25µs : 10µs
          300µs : 240µs
          1ms : 1ms
          10ms : 10ms

          OFF to ON: Max.

          25µs : 50µs
          300µs : 290µs
          1ms : 1.2ms
          10ms : 11ms

          ON to OFF: Typ.

          25µs : 50µs
          300µs : 280µs
          1ms : 1ms
          10ms : 10ms

          ON to OFF: Max.

          25µs : 150µs
          300µs : 390µs
          1ms : 1.2ms
          10ms : 11ms

          Input impedance

          4.3kΩ

          Expansion output unit

          Output Points

          8

          External connectionmethod

          Relay

          MOSFET (N-ch)
          (with overcurrent protection function)*3

          Rated load

          250 VAC/30 VDC, 2 A

          30 VDC, 0.5 A

          Leakage current (when output is OFF)

          100µA or less

          Residual voltage (at ON)

          0.8 VDC or less (with 0.5 A output), 0.6 VDC or less (with 0.3 A output)

          ON resistance

          50mΩ or less

          Common method

          4 points/1 common
          (2 terminals)*1*2

          8 points/1 common
          (4 terminals)*1*4

          Response time

          OFF to ON

          10ms or less

          100 µs or less
          (with a load of 1 mA or more)

          ON to OFF

          200 µs or less
          (with a load of 1 mA or more)

          Relay life

          Electrical : 100000 cycles or more (20 cycles/minute) Mechanical : 20000000 cycles or more

          Relay replacement

          Not possible

          Internal current consumption

          60mA or less

          30mA or less

          Weight

          Approx. 230 g

          Approx. 210 g

          *1 The input COM and output COM terminals are independent.
          *2 The KV-N8EXR has two C1 output terminals and two C2 output terminals, but each pair of these terminals is shared internally. (C1 and C2 are isolated.)
          *3 If even a single overcurrent is detected, the protection operation (output turned OFF) and automatic recovery are repeated for all outputs within the shared common, until the cause of the problem is removed.
          *4 The KV-N8EXT has four COM output terminals, but these terminals are shared nternally.

          Terminal block type: Extension access window cassette

          Model

          KV-N1AW

          Extension access window cassette

          Number of times
          that the product can
          be connected and
          disconnected

          200

          Memory save method

          Flash ROM can be rewritten 10000 times

          General specifications

          Supply voltage

          Supplied from the base unit

          Operating ambient temperature

          0 to +55°C (no freezing)*1*2

          Storage temperature

          -25 to +75°C

          Operating ambient humidity

          5 to 90% RH (no condensation)*3

          Base Unit

          Storage relative humidity

          35 to 85% RH (no condensation)*3

          Noise immunity

          1500 V peak-to-peak or more, pulse width 1 µs, 50 ns (by noise simulator), IEC standard compliant (IEC61000-4-2/3/4/6)

          Vibration resistance

          Intermittent vibration

          Frequency: 5 to 9 Hz

          Amplitude : 3.5 mm*4

          Frequency: 9 to 150 Hz

          Acceleration : 9.8 m/s2*4

          Continuous vibration

          Frequency: 5 to 9 Hz

          Amplitude : 1.75 mm*4

          Frequency: 9 to 150 Hz

          Acceleration : 4.9 m/s2*4

          Shock resistance

          Acceleration : 150 m/s2 , application time : 11 ms, two times in each of the X, Y, and Z directions

          Insulation resistance

          50 MΩ or more
          (500 VDC megger used to perform measurements between power terminal and input terminals, and between all external terminals and case)

          Base Unit

          Altitude

          2000m or less

          Pollution degree

          2

          Weight

          Approx. 30 g

          *1 This is the guaranteed range of the system
          *2 This is regulated according to the temperature 30 mm below the center of the control panel unit.
          *3 At temperature of 40°C or higher, use the product in an environment with an absolute humidity of 90% RH or less at 40°C.
          *4 Conforms to JIS B 3502 and IEC61131-2. Number of scans : 10 times (100 minutes) in each of the X, Y, and Z directions

          Terminal block type: Extension serial communication cassette

          Model

          KV-N10L

          KV-N11L

          Transmission
          specifications

          Electrical termination (Terminator)

          Set with the switch on the front panel of the main unit

          Baud rate

          1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200bps

          Transmission method

          Full duplex

          RS-422A/RS-485 (4-wire) : Full douplex, RS-485 (2-wire) : Half douplex

          Data format

          Start bit

          1 bit

          Data bits

          7 bit, 8 bit

          Stop bits

          1 bit, 2 bit

          Error detection

          Parity

          Even, odd, none

          RS/CS flow control

          Enabled, disabled

          Interface

          Communication standard

          RS-232C

          RS-422A/RS-485 (4-wire), RS-485 (2-wire)

          Connection

          D-sub 9-pin

          European terminal block (cannot be removed or reconnected)

          Transmission
          specifications

          Transmission distance

          15m

          Extendable up to 1200 m*1

          Number of transmission units

          1

          32*1

          Indication

          SD (orange), RD (orange)

          Weight

          Approx. 30 g

          *1 This varies depending on the model. For details, see the KV Nano Series “Serial Communication Function User's Manual.”

          Terminal block type: Analogue I/O unit

          Model

          KV-N3AM

          Conversion

          A/D conversion, D/A conversion

          Points

          A/D conversion : 2 (single end), D/A conversion : 1

          Range/resolution

          Voltage

          -10 V to +10 V

          A/D conversion : 1/8000 2.5 mV, D/A conversion : 1/8000 2.5 mV*1

          0 to 10 V

          A/D conversion : 1/4000 2.5 mV, D/A conversion : 1/4000 2.5 mV*1

          0 to 5 V

          A/D conversion : 1/4000 1.25 mV, D/A conversion : 1/4000 1.25 mV*1

          1 to 5 V

          A/D conversion : 1/3200 1.25 mV, D/A conversion : 1/4000 1.25 mV*1

          Current

          0 to 20 mA

          A/D conversion : 1/4000 5 µA, D/A conversion : 1/4000 5 µA*1

          4 to 20 mA

          A/D conversion : 1/3200 5 µA, D/A conversion : 1/3200 5 µA*1

          Conversion speed

          80 µs/channel*2

          Conversion precision

          Voltage

          Without temperature
          compensation

          A/D conversion : ±0.3% of F.S. (at 25°C ±5°C), ±0.5% of F.S. (at 0 to 55°C), D/A conversion : ±0.3% of F.S. (at 25°C ±5°C), ±0.5% of F.S. (at 0 to 55°C)

          With temperature
          compensation

          A/D conversion : ±0.3% of F.S. (at 25°C ±5°C), D/A conversion : ±0.3% of F.S. (at 25°C ±5°C), ±0.5% of F.S. (at 0 to 55°C)

          Current

          Without temperature
          compensation

          A/D conversion : ±0.4% of F.S. (at 25°C ±5°C), ±0.6% of F.S. (at 0 to 55°C), D/A conversion : ±0.3% of F.S. (at 25°C ±5°C), ±0.5% of F.S. (at 0 to 55°C)

          With temperature
          compensation

          A/D conversion : ±0.4% of F.S. (at 25°C ±5°C), D/A conversion : ±0.3% of F.S. (at 25°C ±5°C), ±0.5% of F.S. (at 0 to 55°C)

          Input resistance

          Voltage

          A/D conversion : 5MΩ

          Current

          A/D conversion : 250MΩ

          Absolute maximum input

          Voltage

          A/D conversion : ±15V

          Current

          A/D conversion : ±30mA

          Isolation method

          Between analogue input

          Isolated (photocoupler, transformer)

          A/D , D/A conversion unit

          Isolation method

          Between Analogue input - output

          Non-isolated

          Isolation method

          Between analogue input channels

          A/D conversion : Non-isolated

          Minimum load resistance

          Voltage

          D/A conversion : 1kΩ

          Maximum load resistance

          Current

          D/A conversion : 600kΩ

          Special functions

          ▼A/D conversion
          Input range switching,
          temperature fluctuation compensation enabling/disabling,
          channel skip, scaling, special data offset,
          peak-/bottom-hold, zero clip, zero shift, comparator,
          averaging (time-specified, count-specified, moving average),
          disconnection detection
          ▼D/A conversion
          Output range switching, output data offset,
          scaling, error hold,
          upper/lower limit alarm, output limit,
          channel skip, output in PROG mode

          Internal current consumption

          120mA or less

          Weight

          200 g

          *1 For the possible measuring range for out-of-range input, refer to “A/D and D/A conversion table” in “KV-N3AM User's Manual.”
          *2 When the temperature fluctuation compensation is used, the temperature fluctuation compensation time of 80 µs will be added regardless of the number of channels being used.

          Connector type: Base unit

          Model

          KV-NC32T

          General specifications

          Supply voltage

          24 VDC (+10%/-15%)

          Operating ambient temperature

          0 to 55°C (no freezing)*1

          Storage temperature

          -25 to +75°C

          Operating ambient humidity

          5 to 95% RH (no condensation)

          Withstand voltage

          1500 VAC for 1 minute, between power supply terminal and I/O terminals and between all external terminals and case
          (1000 VAC for 1 minute, between power supply terminal and output terminals for the transistor output type expansion unit)

          Noise immunity

          1500 V peak-to-peak or more, pulse width 1 µs, 50 ns (by noise simulator), IEC standard compliant (IEC61000-4-2/3/4/6)

          Vibration resistance

          Intermittent vibration

          Frequency: 5 to 9 Hz

          Amplitude: 3.5 mm*2*3

          Frequency: 9 to 150 Hz

          Acceleration: 9.8 m/s2*4

          Continuous vibration

          Frequency: 5 to 9 Hz

          Amplitude: 1.75 mm*4

          Frequency: 9 to 150 Hz

          Acceleration: 4.9 m/s2*4

          Shock resistance

          Acceleration: 150 m/s2, application time: 11 ms, two times in each of the X, Y, and Z directions

          Insulation resistance

          50 MΩ or more
          (500 VDC megger used to perform measurements between power terminal and input terminals, and between all external terminals and case)

          Operating environment

          As little dust and corrosive gases as possible

          Operating altitude

          2000 m or less

          Overvoltage category

          Pollution degree

          2

          Performance specifications

          Calculation control method

          Programme storage method

          I/O control method

          Refresh method

          Programming language

          Expanded ladder, KV Script, mnemonic

          Number of instructions

          Basic instructions: 81 kinds and 182 instructions, Application instructions: 39 kinds and 56 instructions
          Calculation instructions: 123 kinds and 311 instructions, Expansion instructions: 92 kinds and 141 instructions,
          Total: 335 kinds and 690 instructions

          Instruction execution speed

          Basic instruction: 50 ns minimum, Application instruction: 170 ns minimum

          Program capacity

          32k steps

          Maximum number of attachable I/O units

          8

          Maximum number of I/O points

          256 (excluding the base unit I/O)

          Input relay/Output relay/Internal auxiliary relay

          R

          Total of 9600 points 1 bit (R000 to R59915)

          Link relay

          B

          8192 points 1 bit (B0 to B1FFF)

          Internal auxiliary relay

          MR

          9600 points 1 bit (MR000 to MR59915)

          Latch relay

          LR

          3200 points 1 bit (LR000 to LR19915)

          Control relay

          CR

          1440 points 1 bit (CR000 to CR8915)

          Timer

          T

          512 points 32 bits (T0 to T511)

          Counter

          C

          256 points 32 bits (C0 to C255)

          Data memory

          DM

          32768 points 16 bits (DM0 to DM32767)

          Link register

          W

          16384 points 16 bits (W0 to W3FFF)

          Temporary memory

          TM

          512 points 16 bits (TM0 to TM511)

          High-speed counter

          CTH

          3 points (CTH0 to CTH2)
          32-bit automatic reset counter*5 (Input response: 100 kHz per single phase, 50 kHz per phase difference)*6

          High-speed
          counter comparator

          CTC

          6 points (CTC0 to CTC5)
          32 bits, two points per high-speed counter

          Index register

          Z

          12 points 32 bits (Z01 to Z12)

          Control memory

          CM

          9000 points 16 bits (CM0 to CM8999)

          Positioning pulse output

          3 axes
          Maximum output frequency: 100 kHz

          Base unit I/O

          Input: 16 points, output: 16 points
          Input common: 1 point, Output common: 1 point

          Number of comments and
          labels that can be stored
          in the main unit

          Device comment

          20000
          When a maximum-length ladder programme is written with no labels.

          Label

          28000
          When a maximum-length ladder programme is written with no device comments.

          Power off hold function

          Programme memory

          Flash ROM can be rewritten 10000 times

          Device

          Nonvolatile RAM*7

          Clock function

          ±60 seconds/month (at 25°C)

          Self-diagnosis function

          CPU error, RAM error, and other problems

          Input specifications

          Relay number

          General input: R000 to R009 (10 points), High-speed A-phase and B-phase input: R010 to R015 (6 points)

          Input mode

          24 VDC input (open collector)

          Maximum input voltage

          26.4 VDC

          Rated input voltage

          24 VDC (General input: 5.3 mA, High-speed A-phase and B-phase input: 6.5 mA*8)

          Minimum ON voltage

          19 VDC

          Maximum OFF current

          1.5 mA

          Common method

          All points/1 common (1 terminal)

          Circuit delay time

          General input: OFF to ON Max. 30 µs (Typ. 3.5 µs), ON to OFF Max. 50 µs (Typ. 15 µs)
          High-speed A-phase and B-phase input: OFF to ON Max. 2 µs (Typ. 1.1 µs), ON to OFF Max. 2 µs (Typ. 0.3 µs)*9

          Input time constant

          Normal: 10 ms, When the HSP instruction is used: 10 µs
          When CR2305 is turned ON: 10 µs to 10 ms, eight-level switching is possible (set with CM1620). Can also be set from the Unit Editor.*9

          Delay by input time constant
          Input time constant setting 10 µs: Digital filter 1.6 to 2 µs
          Input time constant setting 20 µs: Digital filter 9 to 12 µss
          Input time constant setting 110 µs: Digital filter 90 to 93 µs
          Input time constant setting 500 µs: Digital filter 300 to 400 µs
          Input time constant setting 1 ms: Digital filter 800 to 900 µs
          Input time constant setting 2.5 ms: Digital filter 2.3 to 2.4 ms
          Input time constant setting 5 ms: Digital filter 4.0 to 4.5 ms
          Input time constant setting 10 ms: Digital filter 9 to 9.5 ms

          Response frequency

          (High-speed A-phase and B-phase input) Single phase: 100 kHz, phase difference: 50 kHz, 24 V±10%, Duty 50%

          Output specifications

          Relay number

          General output: R506 to R515 (10 points), High-speed output: R500 to R505 (6 points)

          Output mode

          MOSFET (N-ch)

          Rated load

          30 VDC
          General output: 0.2 A (1.6 A/common), High-speed output: 0.3 A (1.6 A/common)

          Maximum OFF voltage

          30 VDC

          Leakage current at OFF

          100 µA or less

          Residual voltage at ON

          0.6 VDC or less

          Common method

          16 points/1 common

          ON/OFF response time

          General output:
          OFF to ON : 100 µs (load of 1 mA or more), ON to OFF : 200 µs (load of 1 mA or more)
          High-speed output:
          OFF to ON: 2 µs (load of 7 mA or more), ON to OFF: 5 µs (load of 7 mA or more)

          Overcurrent protection

          Protection provided for each common*10

          Output frequency

          High-speed output: 100 kHz (7 to 100 mA load)

          Built-in serial port

          Interface

          Communication standard

          RS-232C

          Connection

          Modular connector

          Transmission specifications RS-232C

          Baud rate

          1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps

          Transmission method

          Full duplex

          Data format

          Start bit

          1 bit

          Data bits

          7 bits, 8 bits

          Stop bits

          1 bit, 2 bits

          Error detection

          Parity

          Even, odd, none

          Transmission distance

          15 m

          Number of transmission units

          1

          Indication

          Common between SD/RD
          SD: (green), RD: (red)
          The colour may appear as orange during transmission.

          Internal current consumption

          260 mA

          Weight

          Approx. 220 g

          *1 The temperature below the unit centre (30 mm) inside a control panel.
          *2 These specifications correspond to situations in which the unit is mounted on a DIN rail and in which the unit is mounted on the panel directly.
          *3 Conforms to JIS B 3502 and IEC61131-2, Number of scans: 10 times (100 minutes) in each of the X, Y, and Z directions
          *4 Conforms to JIS B 3502 and IEC61131-2. Number of scans: 10 times (100 minutes) in each of the X, Y, and Z directions
          *5 You can also configure the settings so that automatic reset is not used.
          *6 Only open collectors are supported. Line drivers are not supported.
          *7 You can set the target device by clicking "CPU system setting" and then "Power off holding" in KV STUDIO.
          *8 Reference value of input current.
          *9 The input response time corresponding to the input time constant can be calculated as shown below. (Response time) = (Circuit delay of the input circuit) + (Delay by the digital filter)
          Example: Maximum response time when the input time constant is set to 10 µs
          OFF to ON/ON to OFF: 2 µs (circuit delay) + 2 µs (digital filter) = 4 µs
          Example: Maximum response time when the input time constant is set to 500 µs
          OFF to ON: 30 µs (circuit delay) + 400 µs (digital filter) = 430 µs, ON to OFF: 50 µs (circuit delay) + 400 µs (digital filter) = 450 µs
          *10 If an overcurrent occurs, the protection operation (output turned OFF) and automatic recovery are repeated for all outputs within the shared common until the cause of the problem is removed.

          Connector type: Expansion input unit

          Model

          KV-NC16EX

          KV-NC32EX

          Expansion input unit

          External connection method

          Connector

          Input Points

          16 points

          32 points

          Input terminals

          24 VDC mode, 5 VDC mode

          Maximum input voltage

          26.4 VDC

          Input rated voltage

          24 VDC mode

          5.2 mA

          5 VDC mode

          1 mA

          Minimum ON voltage

          24 VDC mode

          19 V

          5 VDC mode

          3.5 V

          Maximum OFF voltage

          24 VDC mode

          1.5 mA

          5 VDC mode

          1.5 V

          Common method

          16 points/1 common (2 terminals)*1

          32 points/1 common (2 terminals)*1

          Input time constant (four-level switching)

          Input time constant setting

          OFF to ON: Typ.

          25 µs: 10 µs
          300 µs : 240 µs
          1 ms: 1 ms
          10 ms: 10 ms

          OFF to ON: Max.

          25 µs: 50 µs
          300 µs : 290 µs
          1 ms: 1.2 ms
          10 ms: 11 ms

          ON to OFF: Typ.

          25 µs: 50 µs
          300 µs : 280 µs
          1 ms: 1 ms
          10 ms: 10 ms

          ON to OFF: Max.

          25 µs: 150 µs
          300 µs : 390 µs
          1 ms: 1.2 ms
          10 ms: 11ms

          Input impedance

          4.4 kΩ

          Internal current consumption

          20 mA or less

          Weight

          Approx. 100 g

          Approx. 110 g

          *1 The KV-NX16EX and KV-NC32EX have 2 COM terminals, but these are shared internally.

          Connector type: Expansion ounput unit

          Model

          KV-NC8ER

          KV-NC16ET

          KV-NC32ET

          Expansion output unit

          External connectionmethod

          Relay

          MOSFET output (With overcurrent protection function)*2*3

          MOSFET output (With overcurrent protection function)*7*3

          External connection method

          European terminal block

          Connector

          Rated load

          250 VAC/30 VDC, 2 A

          30 VDC, 0.2 A*4

          Leakage current (when output is OFF)

          100 µA or less

          Residual voltage (at ON)

          0.6 VDC or less

          ON resistance

          50mΩ or less

          Common method

          4 points/1 common (8 terminals)*1

          16 points/1 common (2 terminals)*5*6

          32 points/1 common (2 terminals)*5*8

          Response time

          OFF to ON

          10 ms or less

          100 µs or less (with a load of 1 mA or more)

          ON to OFF

          200 µs or less (with a load of 1 mA or more)

          Relay life

          Electrical : 100,000 cycles or more (20 cycles/minute) Mechanical : 20,000,000 cycles or more

          Relay replacement

          Not possible

          Internal current consumption

          70 mA or less

          30 mA or less

          50 mA or less

          Weight

          Approx. 130 g

          Approx. 100 g

          Approx. 110 g

          *1 The KV-NC8ER has four C0s and four C1s, and each set of C0s and C1s is shorted internally.(The sets of C0s and C1s are independent.)
          *2 If even a single overcurrent is detected, the protection operation (output turned OFF) and automatic recovery are repeated for all outputs within the shared common (The outputs within the shared common that are protected when an overcurrent is detected are outputs 000 to 007 or 008 to 015 for the KV-NC16ET(P) and KV-NC16ET(P)E.), until the cause of the problem is removed.
          *3 Sink output types use MOSFET (N-ch) output. Source output types use MOSFET (P-ch) output.
          *4 The rated load of each common terminal is 1.6.
          *5 The KV-NC16ET(P), KV-NC16ET(P)E, and KV-NC32ET(P) COM terminals are shorted internally.
          *6 The outputs within the shared common that are protected when an overcurrent is detected are outputs 000to 007 or 008 to 015 for the KV-NC16ET(P) and KV-NC16ET(P)E.
          *7 If even a single overcurrent is detected, the protection operation (output turned OFF) and automatic recovery are repeated for all outputs within the shared common (The outputs within the shared common that are protected when an overcurrent is detected are outputs 000 to 015 or 100 to 115 for the KV-NC32ET(P).), until the cause of the problem is removed.
          *8 For KV-NC32ET(P), the outputs within the shared common that are protected when overcurrents are detected,
          are outputs 000 to 015, or outputs 100 to 115.

          Connector type: A/D & D/A conversion unit

          Model

          KV-NC4AD

          KV-NC2DA

          Conversion

          A/D conversion

          D/A conversion

          Points

          4 (single end)

          2

          Range/resolution

          Voltage

          -10 V to +10 V

          1/8000 2.5mV

          0 to 10 V

          1/4000 2.5mV

          0 to 5 V

          1/4000 1.25mV

          1 to 5 V

          1/3200 1.25mV

          Current

          0 to 20 mA

          1/4000 5µA

          4 to 20 mA

          1/3200 5µA

          Conversion speed

          80 µs/channel*1

          80µs/CH

          Conversion precision

          Voltage

          Without temperature
          compensation

          ±0.3% of F.S. (at 25°C ±5°C)
          ±0.5% of F.S. (at 0 to 55°C)

          With temperature
          compensation

          ±0.3% of F.S. (at 0 to 55°C)

          ±0.3% of F.S. (at 25°C ±5°C)
          ±0.5% of F.S. (at 0 to 55°C)

          Current

          Without temperature
          compensation

          ±0.4% of F.S. (at 25°C ±5°C)
          ±0.6% of F.S. (at 0 to 55°C)

          With temperature
          compensation

          ±0.4% of F.S. (at 0 to 55°C)

          Input resistance

          Voltage

          5MΩ

          Current

          250Ω

          Absolute maximum input

          Voltage

          ±15V

          Current

          ±30mA

          Isolation method

          Between analogue input

          Isolated (photocoupler, transformer)

          Between analogue input channels

          Non-isolated

          Minimum load resistance

          Voltage

          1kΩ

          Maximum load resistance

          Current

          600Ω

          Special functions

          Input range switching,
          temperature fluctuation compensation enabling/disabling,
          channel skip, scaling, special data offset,
          peak-/bottom-hold, zero clip, zero shift, comparator,
          averaging (time-specified, count-specified, moving average),
          disconnection detection

          Output range switching, output data offset,
          scaling, error hold,
          upper/lower limit alarm, output limit,
          channel skip, output in PROG mode

          *1 When the temperature fluctuation compensation is used, the temperature fluctuation compensation time of 80 µs will be added regardless of the number of channels being used.

          Connector type: Temperature input unit

          Model

          KV-NC4TP

          Temperature input unit

          Number of inputs

          4*1

          Input

          Thermocouple, Platinum resistance thermometer

          Input range

          Thermocouple

          K : -270.0 to 1372.0˚C
          J : -210.0 to 1200.0˚C
          T : -270.0 to 400.0˚C
          E : -270.0 to 1000.0˚C
          N : -270.0 to 1300.0˚C
          R : -50.0 to 1768.0˚C
          S : -50.0 to 1768.0˚C
          B : 0.0 to 1820.0˚C
          WRe5-26 : 0.0 to 2315.0˚C

          Platinum resistance thermometer

          Pt100 : -200.0 to 850.0˚C
          JPt100 : -200.0 to 600.0˚C

          Overall accuracy

          Thermocouple

          ±0.2% of F.S. (at 25°C ±5°C)
          ±0.4% of F.S. (at 0 to 55°C)

          Platinum resistance thermometer

          Allowable wiring resistance

          100 Ω max./wire
          (no variation allowed among
          three wires)

          Conversion speed

          125ms/ch

          Isolation method

          Between input terminals and base unit :
          Photocoupler/semiconductor relay/transformer isolation
          Between channels : (When resistance thermometer is not used) :
          Semiconductor relay isolation :
          When resistance thermometer is used : No isolation

          Special functions

          Channel skip, disconnection detection,
          averaging (time average, count average, moving average),
          special data offset, peak-/bottom-hold, alarm function,
          abnormal input setting function

          Internal current consumption

          40mA or less

          Weight

          Approx. 110 g

          *1 Individual setting is possible for each channel.

          Connector type: EtherNet/IP™ unit

          Model

          KV-NC1EP

          EtherNet/IP™ unit (communication specifications)

          CIP service

          Cyclic
          communication

          Number of connections

          64*1

          RP I (communication cycle)

          0.5 to 10000 ms (0.5 ms increments) Setting is possible for each connection.
          (Data is updated on the line at specified cycles, independent of the number of nodes.)

          Transmission trigger: Output to the adapter

          Cyclic

          Transmission trigger: Input from the adapter

          Cyclic / Change of state*2

          Cyclic communication

          Tolerable communication bandwidth for cyclic communication (@504 bytes)

          6000 (pps)*3

          Tolerable communication bandwidth for cyclic communication (@1444 bytes)

          3000 (pps)*3

          Cyclic
          communication

          Maximum number of refresh words

          8k words

          Maximum data size per connection

          504 bytes or 1444 bytes*4

          Multicast filter function

          Provided (IGMP client function)*5

          Message communication

          Class 3 (connection type): Server

          No. of connections : 64*6

          UCMM (non-connection type): Client

          No. of simultaneous messages : 32

          UCMM (non-connection type): Server

          No. of simultaneous messages : 96

          EtherNet/IP™ conformance test

          Conforming to CT10

          EtherNet/IP™ unit (performance specifications)

          PC applications

          No. of sockets TCP : 8 UDP : 0 Port number : 8500 (can be set within the range between 1 and 65535)*7

          Host link communication

          No. of sockets TCP : Total : 15 UDP : 1 Port number : 8501 (can be set within the range between 1 and 65535)*8*9

          MC protocol communication

          No. of sockets TCP : Total : 15 UDP : 1 Port number : 5000 (can be set within the range between 1 and 65535)*8*9*10

          VT3 connection

          No. of sockets TCP : 0 UDP : 1 Port number : 8502 (can be set within the range between 1 and 65535)

          FTP server

          No. of sockets TCP : 4 Port number : 20, 21

          Clock data automatic adjustment

          No. of sockets UDP : 1 Port number : 123

          E-mail transmission (SMTP, POP3)

          No. of sockets TCP : 2 Port number : 25, 110

          DNS

          No. of sockets UDP : 1 Port number : 53

          FTP client

          No. of sockets TCP : 2 Port number : 20, 21 (can be set within the range between 1 and 65535)

          Easy PLC link

          No. of sockets UDP : 1 Port number : 5001 (can be set within the range between 1 and 65535)

          EtherNet/IP™ cyclic communication function

          No. of sockets TCP : Total : 320 UDP : 1 Port number : 2222

          EtherNet/IP™ message communication function

          No. of sockets TCP : Total : 320 UDP : 1 Port number : 44818

          Internal current consumption

          90mA or less

          Weight

          Approx. 110 g

          *1 The number of connection may exceed 64 where the KV-NC1EP is connected with the multicast of cyclic communication from the originator. The operation of the KV-NC1EP, however, is guaranteed up to 64 connections.
          *2 Communication can be established with equipment that outputs data in the "Change of state" method (send data when any change occurs). The KV-NC1EP cannot output data in the Change of state method.
          *3 Abbreviation of "Packet Per Second," meaning the number of packets that can be sent/received in a second.
          *4 The simultaneity of data in the connection is guaranteed. When 505 bytes or more are used, the equipment to be used must support Large Forward Open (CIP option specification).
          *5 The KV-NC1EP has the IGMP client function that allows filtering of unnecessary multicast packets when the Ethernet switch supporting IGMP Snooping is used.
          *6 The value 64 indicates the total connections including those used by the cyclic communication function. Even when the total connection exceeds 64, the operation of the KV-NC1EP is guaranteed up to 64 connections.
          *7 KV STUDIO, KV COM+
          *8 TCP sockets and UDP socket can be used simultaneously.
          *9 Up to 15 TCP sockets can be used in total.
          *10 Port numbers can be assigned individually to TCP and UDP sockets.

          Connector type: Serial communication adapter

          Model

          KV-NC10L

          KV-NC20L

          Transmission
          specifications

          Electrical termination (Terminator)

          Set with the switch on the front panel of the main unit

          Baud rate

          1200,2400,4800,9600,19200,38400,57600,115200bps

          Transmission method

          Full duplex

          Port 1 : Full duplex
          Port 2 : Full duplex, Half duplex

          Data format

          Start bit

          1 bit

          Data bits

          7 bit, 8 bit

          Stop bits

          1 bit, 2 bit

          Error detection

          Parity

          Even, odd, none

          RS/CS flow control

          Enabled, disabled

          Port1 : Enabled, disabled

          Interface

          Communication standard

          RS-232C

          Port 1 : RS-232C
          Port2 : RS-232C, RS-422A/RS-485 (4-wire), RS-485 (2-wire)

          Connection

          D-sub 9-pin

          Port 1 : D-sub 9-pin
          Port 2 : European terminal block

          Transmission
          specifications

          Transmission distance

          15m

          Port1 : 15 m
          Port2 : 15 m, Extendable up to 1200 m

          Number of transmission units

          1

          Port1 : 1
          Port2 : 1, 32

          Indication

          SD (orange), RD (orange)

          Weight

          Approx. 100 g

          Approx. 110 g